SIEL Green Point


Project Description
green-point02

Suitable for

Banks
> Telecommunications
> industrial centers
> security systems
> Intelligent fuel system
>Rack Mounted Server and network equipment
> Office-Commercial-Stores Centers

Available in single-phase (1/10kVA) also in rack version, and three/single-phase (10/20 kVA) with DSP microprocessor control for the best reliability. This inverter is provided with IGBT, PWM technology, VFI-SS-111 double conversion (Voltage Frequency Independent by the .CEIEN62040-3), LCD display, RS232 communication port and intelligent slot for AS400-SNMP, communication software, upgradable batteries, internal maintenance manual by-pass; up to 3 units can work in parallel mode

atributies

> UPS power: 1-20KVA
Input nominal Voltage: 176-277V in Single phase entry and 304-478V in Three phase entry
>  adjustable input frequency  50/60 Hz
>  Input Power Factor at nominal input voltage and normal load  0.98 for 1-10KVA  and 0.99 for 10-20 KVA
> output nominal Voltage: 200/208/220/230/240 (1±2%)VAC
Static voltage stability: for 1-3 KVA = ±2% and for 1-3 KVA = ±1%
> Dynamic voltage stability < ± 5
> SINGLE – PHASE:1-10KVA and TRI / SINGLE-PHASE : 10-20KVA
> Linear full load THD <  2% for 10-20 KVA

green-poin-a01
green-poin-b-01

> RS232 communication port and intelligent slot for AS400-SNMP, communication software
Operating temperature: 0ºC – 45ºC
>  Operating humidity < 95%
>  IGBT inverter with PWM technology
>  Upgradable batteries
> Overload for 10 minutes = 1,3Pn for 1-3KVA and 1.25Pn for 6-10KVA (SINGLE – PHASE)-1.3Pn for 10-20KVA (TRI / SINGLE-PHASE)

>Dimension: 

220*145*400mm for 1KVA

347*192*460mm for 2KVA

347*1928460mm for 3KVA

708*260*550mm for 6KVA

708*260*550mm for 10KVA (SINGLE – PHASE)

890*350*650mm for 10-20KVA (TRI / SINGLE-PHASE)

>  Weight:

13kg  for 1KVA

31kg for 2KVA

32kg for 3KVA

80kg for 6KVA

84kg (34kg without batteries) for 10KVA (SINGLE – PHASE)

127kg (45kg without batteries) for 10KVA

188kg (50kg without batteries) for 20KVA (TRI / SINGLE-PHASE)

Input Power Factor at nominal input voltage and normal load > 0.98 for 1-3 KVA, 0.99 for 6-10KVA (SINGLE – PHASE)
Input Power Factor at nominal input voltage and normal load > 0.99 for 10-20 KVA (TRI / SINGLE-PHASE)

>  Linear full load THD <2%
>  EPO port for emergency shutting down
> Up to 3 units can work in parallel mode
> National and international complaints: CEI EN 62040 – 1 – 2:2003, CEI EN 62040 – 2:2006 , CEI EN 62040 – 3:2002
> Noise at 1 meter (ISO3476) (dBA): < 45 FOR 1-10KVA (SINGLE – PHASE) and  < 55 FOR 10-20 KVA (TRI / SINGLE-PHASE)
> Battery temperature suggested (°C): 15-25°C